新型平板热管换热器热回收特性实验研究  被引量:4

Novel Plate Heat Pipe Heat Exchanger for Heat Recovery Characteristics in Room Ventilation

在线阅读下载全文

作  者:赵耀华[1] 于雯静[1] 刁彦华[1] 张冀[1] 郝丽敏[1] 

机构地区:[1]北京工业大学建筑工程学院,北京100124

出  处:《北京工业大学学报》2012年第4期497-501,共5页Journal of Beijing University of Technology

基  金:国家自然科学基金资助项目(50376064/E060308)

摘  要:针对普通住宅日常通风换气的特点设计出一台小型平板热管通风换热器,在不同风量(60、90、120、150m3/h)和室内外温差(室外新风温度为27~40℃,室内排风温度控制在24℃)的条件下,针对夏季工况,进行了热管换热器的真空度对其热回收效率影响的实验研究.实验结果表明,该热管换热器热回收效率较高,最高热回收效率接近60%;在风量较高的情况下,真空度对其热回收效率影响很小.A plate heat pipe heat exchanger for room ventilation is designed. Its performance affected by vacuum is experimentally investigated. Experiments were carried out under the simulated summer condition. The air volume rates were changed at 60, 90, 120, and 150 m3/h. The fresh air temperature varied from 27 to 40 ℃, whereas the return air temperature was kept at about 24 ℃. Results show that the conservation effect of the heat pipe heat exchanger is prominent and the maximum effectiveness is about 60%. The change for effectiveness is slightly different from variation of vacuum.

关 键 词:平板热管 热回收 真空度 建筑节能 通风换气 

分 类 号:TU834[建筑科学—供热、供燃气、通风及空调工程]

 