检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]广东电网广州供电局变电一部,广东广州510180 [2]武汉大学电气工程学院,湖北武汉430072
出 处:《电力自动化设备》2012年第4期138-141,共4页Electric Power Automation Equipment
摘 要:小电阻在城市配网的接入方式会影响主变保护动作情况和配网零序网络。针对输配电网中2种不同等级的变电站,分析了曲折变接于变低套管与变低开关之间和接于变低10 kV母线2种接线方式下,配网接地故障时保护的动作情况,比较了10 kV自投动作后2种接线方式对配网零序网络的改变。得出当110 kV变电站曲折变接于变低开关和变低套管之间时,曲折变本体故障不会影响10 kV母线,同时主变跳闸切除多余曲折变,能保证10 kV配网在备自投动作后零序网络稳定。220 kV变电站中曲折变通过开关接在母线上,若曲折变故障后开关拒动,变低后备动作隔离故障,不影响变中供电可靠性。为了维持城市配网接地点的唯一性,保证曲折变保护正确动作,建议10 kV备自投联切曲折变。The mode of low-resistance connection to urban distribution network will affect the action of main transformer protection and the zero-sequence network of distribution network. The actions of protection during grounding fault in substations of two different levels in transmission and distribution grid are analyzed for two connection modes of winding transformer:between low-voltage switch and low-voltage bushing of main transformer in 110 kV substation;with 10 kV bus in 220 kV substation. The changes of zero-sequence network after the action of 10kV ASD(Automatic Switching Device) are compared for both modes. In the first mode,the body failure of winding transformer will not affect 10 kV bus while the redundant winding transformer of main transformer will be tripped to keep its zero-sequence network stable. In the second mode,when the winding transformer fails ,if the switch refuses to act but the low-voltage backup protection of main transformer acts to isolate fault,the supply reliability will not be affected. To maintain the uniqueness of grounding point for urban distribution network and ensure the correct action of winding transformer protection,it is suggested the 10 kV ASD to trip the redundant winding transformer.
关 键 词:配电 曲折变 零序网络 备自投 接地 变电站 变压器 保护
分 类 号:TM727.2[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.28