交直流混联电网发电机失步保护与直流低电压保护协调  被引量:4

Coordination of Out-of-step Protection and DC Under-voltage Protection in AC-DC Hybrid Grids

在线阅读下载全文

作  者:张健康[1,2] 索南加乐[1] 粟小华 焦在滨[1] 

机构地区:[1]西安交通大学电气工程学院,陕西省西安市710049 [2]西北电网有限公司,陕西省西安市710048

出  处:《电力系统自动化》2012年第8期92-97,共6页Automation of Electric Power Systems

基  金:国家自然科学基金资助项目(51037005);高等学校博士学科点专项科研基金资助项目(20090201120018)~~

摘  要:直流输电站间通信中断情况下,当逆变侧出现故障紧急停运时,整流侧主要依靠直流低电压保护动作实现闭锁。由于整流侧通常采用定功率控制,换流器会出现低电压大电流运行并吸收大量的无功功率,若交流系统强度不够就容易造成整流侧交流母线电压大幅降低,进而引起周围发电厂内机组出现振荡直至失步。文中通过分析一起直流系统长时间低电压运行引起发电机失步保护动作的实例,指出换流站直流低电压保护应与邻近发电机失步保护相互协调,并提出了配合原则。所述原则已应用于实际直流输电工程及其邻近发电厂,显著提高了交直流混联电网运行可靠性。During communication failure between converter stations, if emergency switch off sequence (ESOF) occurs at inverter side due to serious faults, it mainly depends on DC under-voltage protection to block converter at rectifier side. Constant power control is usually employed at rectifier side, therefore, blocking with bypass pair at inverter side frequently leads to low voltage and large current operation mode of rectifier station. This adversely affects the adjacent AC grid and makes the voltage in AC bus of .converter station reduce rapidly. As a result, the adjacent generators may start oscillating and even lose synchronism. Based on the analysis of mal-operation of generator out-of-step protection resulting from high voltage direct current (HVDC) under-voltage operation, it is concluded that both out-of-step protection and DC under-voltage protection should coordinate with each other properly successfully applied to HVDC projects and protection greatly, in AC-DC hybrid grid. and the principle of setting cooperation their adjacent AC power plants in China, is proposed. This method has been which improves the performance of

关 键 词:交直流混联电网 直流输电 失步保护 低电压保护 

分 类 号:TM772[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象