作 者:ZHANG Linli XU Bingyin XUE Yongduan GAO Houlei
机构地区:[1]Shandong University [2]Shandong University of Technology [3]China University of Petroleum (East China)
出 处:《中国电机工程学报》2012年第13期I0015-I0015,198,共1页Proceedings of the CSEE
基 金:国家863高技术基金项目(2012AA050213);国家自然科学基金项目(51077090,51177096).
摘 要:为解决配电网小电流接地故障时故障点定位困难的问题,提出一种基于线电压和零模电流暂态分量的故障定位新方法。该方法借助馈线自动化(feeder automation,FA)系统实现,不需要额外增加设备。馈线终端检测线电压和零模电流信号,利用暂态线电压的希尔伯特变换与暂态零模电流的乘积计算故障方向参数,FA主站根据故障点前后方向参数极性相反的特征确定故障点所在的线路区段。介绍基于线电压的小电流接地故障检测和接地故障相确定的算法。数字仿真与试验结果表明该方法是正确可行的。Non-solidly earthed systems are widely used for middle voltage distribution network at home and abroad. Fault point location especially the single phase-to-earth fault is very difficult because the fault current is very weak and the fault arc is intermittent. Although several methods have been developed, the problem of fault location has not yet been resolved very well. A new fault location method based on transient component of line voltage and 0-mode current is presented in this paper, which can realize fault section location by the feeder automation (FA) system. Line voltage signal can be obtained conveniently without requiring any additional equipment. This method is based on transient information, not affected by arc suppression coil.
关 键 词:低压配电网络 瞬态故障 定位方法 接地电流 线电压 非直接接地系统 单相接地故障 馈线自动化