火力发电厂分散控制系统中RS-232接口浪涌保护器的设计  被引量:6

Design of Surge Protective Device for RS-232 Data Interface in DCS of Coal-Fired Power Plants

在线阅读下载全文

作  者:商鹏[1] 肖稳安[1] 柴健[1] 

机构地区:[1]南京信息工程大学,江苏南京210044

出  处:《低压电器》2012年第8期14-17,共4页Low Voltage Apparatus

基  金:公益性行业科研专项(GYHY200806014)

摘  要:根据火力发电厂分散控制系统(DCS)信号传输的特点、RS-232数据接口的电气特性,结合理论分析,提出一种RS-232数据接口浪涌保护器(SPD)的结构设计方案。通过大量的试验,对退耦电阻阻值的选取作了较为详尽的分析,并证明该SPD在浪涌电流冲击测试下,能够有效地将残压值限制在设备耐受的范围内,以保护后续电子设备。同时,该SPD接入系统后,对信号传输影响较小,能够保证系统的正常运行。According to the characteristics of signal transmission in the distributed layered control system of coal-fired power plants,and the electrical property of RS-232 data interface,combining with theoretical analysis,a design scheme of surge protective device(SPD) structure for RS-232 data was brought up.A large number of experiments were used to make a detailed analysis for the selection of decoupling resistance,and it was proved that this SPD could effectively limit residual pressure value in the range of equipment tolerance in the transient current shock test.Meanwhile,when SPD accesses the systerm,it has little influence to signal transmission and can ensure the normal operation of the system.

关 键 词:浪涌保护器 分散控制系统 RS-232数据接口 退耦电阻 

分 类 号:TM862[电气工程—高电压与绝缘技术] TN915.05[电子电信—通信与信息系统]

 