检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]国家电网公司运行分公司晋东南管理处,山西长治046603
出 处:《电力电容器与无功补偿》2012年第3期49-55,共7页Power Capacitor & Reactive Power Compensation
摘 要:从电容器内部结构出发简单介绍了电容器内熔丝保护原理,电容器内部元件如果发生绝缘击穿,与之串联的内熔丝熔断,电容器组电容会发生相应变化,最终导致不平衡电流的变化。文章对两种典型的电容器组双桥差不平衡电流保护进行了计算和分析,推出简易的计算公式,并通过电容器组的实际运行数据对其应用加以验证。In this paper, the principle of the protection of the capacitor with internal fuse is intro- duced briefly according to the internal structure of the capacitor, if the internal components of the capacitor breakdown, the series internal fuse in fuse, the capacitance wiU change accordingly, and will lead to the changes of the unbalanced current ultimately. In this paper, two kinds of typical pro- tection on double differential current bridges of large capacity capacitor bank are calculated and ana- lyzed, a simple formula is derived, and according to actual operating data, the practical applications are verified.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.28