线路光差保护改载波保护运行探讨与实践  

Discussion and practice on line carrier protection replacing optical differential protection

在线阅读下载全文

作  者:晋斌[1] 

机构地区:[1]贵阳供电局,贵州贵阳550002

出  处:《贵州电力技术》2012年第9期81-82,40,共3页Guizhou Electric Power Technology

摘  要:阐述了在500kV大黔双回线、黔烽Ⅰ回线停电加固期间500kV黔烽Ⅱ回线路光差保护没有光纤通道,临时将黔烽Ⅱ回线路光差保护改造成载波保护运行,成功解决了在500kV大黔双回线、黔烽Ⅰ回线停电加固期间,黔烽Ⅱ回线路只单主保护运行。This paper expounded the 500 kV Qianfeng Ⅱ back line had not fiber channel for optical differential protection during the 500 kV Daqian double line and Qianfeng Ⅰ back line at the time what power failure and reinforcement. Temporarily transformed Qianfeng Ⅱ back line optical differential protection into carrier protection operation, successfully solved the problem of Qianfeng Ⅱ back line only single primary protection operation during the 500 kV Daqian double line and Qianfeng Ⅰ back line power failure and reinforcement.

关 键 词:光差保护 载波保护 保护改造 通道改造 

分 类 号:TM63[电气工程—电力系统及自动化]

 