检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]北京工业大学环境与能源工程学院,北京100124
出 处:《北京工业大学学报》2012年第10期1554-1559,共6页Journal of Beijing University of Technology
基 金:国家自然科学基金资助项目(51076003);教育部高等学校博士学科点专项科研资金资助项目(200800050010)
摘 要:为了降低通信基站空调的耗电量,提出利用热虹吸管换热机组辅助空调为基站降温的节能方案,研制出空气-空气热虹吸管换热机组样机,并对样机进行了实验测试.结果表明,在实验工况范围内,换热机组运行稳定、可靠,换热效果良好,温度效率η可达50%,能效比EER可达10.9。To reduce the power consumption of air conditioners used for cooling telecommunication base stations,the thermosyphon heat exchanger unit is presented for the base station heat dissipation assisting with the air conditioner.An air to air thermosyphon heat exchanger unit is designed and tested.Results indicate that the heat exchanger unit works well with good heat dissipation performance under the testing conditions.The temperature effectiveness of the unit can reach 50%,and the energy efficiency ration(EER) reaches 10.9.
分 类 号:TU83[建筑科学—供热、供燃气、通风及空调工程]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.117