国产无间隙金属氧化物避雷器用于±660kV高压直流输电工程直流滤波器的暂态应力分析  被引量:1

The Transient Stress Analysis of DC Filter in ±660 kV HVDC Transmission by Using Domestic Gap-free ZnO Arresters

在线阅读下载全文

作  者:孙伟 张雷 

机构地区:[1]西安西电电力系统有限公司,西安710075

出  处:《电瓷避雷器》2012年第5期34-38,44,共6页Insulators and Surge Arresters

摘  要:为了研究换流站直流滤波器避雷器的最苛暂态应力,结合宁东-山东±660 kV高压直流输电工程银川东站直流滤波器的配置,使用某公司提供的避雷器电阻片伏安特性,对直流滤波器避雷器在近区故障和远端故障时的暂态应力进行了仿真分析。研究结果得到了直流滤波器避雷器的最苛刻暂态应力,为确定直流滤波器各设备的绝缘水平提供了依据;同时也验证了避雷器电阻片的实用性,能够满足工程建设的需要。In order to study the most severe transient stress of the DC filter arresters converter station, The author works on the simulation analysis of several fault modes by using the arrester V-I characteristics and combining with the DC filter configuration in Yinchuan East Station of Ningdong to Shandong ±660 kV HVDC transmission project. The result gives the most severe stress of the DC filter arrester, which provides the insulation level of the DC filter equipment, and proves practicability of the arrester V-I characteristics can meet the requirements of HVDC construetion.

关 键 词:直流滤波器 无间隙金属氧化物避雷器 暂态应力 绝缘水平 电磁暂态计算程序 

分 类 号:TM862[电气工程—高电压与绝缘技术]

 