直驱永磁同步风电机组不对称故障穿越的研究  

Asymmetrical faults ride-through of directly driven wind turbine with permanent magnet synchronous generator

在线阅读下载全文

作  者:杜韦辰[1] 

机构地区:[1]兰州石化职业技术学院电子电气工程系,兰州730060

出  处:《工业仪表与自动化装置》2012年第5期8-11,共4页Industrial Instrumentation & Automation

基  金:甘肃省教育厅科研项目(1015B-02)

摘  要:在分析不对称电网电压条件下直驱永磁风力发电机组并网逆变器数学模型的基础上,提出了正负序双电流闭环控制策略,完成风力发电机组在电网发生不对称故障下的不脱网运行。在PSCAD/EMTDC环境下建立基于IGBT背靠背变频器的1.5 MW永磁直驱风力发电系统仿真模型,仿真结果证明该控制策略的可行性。According to the performance analysis of the mathematical model of the three-phase grid- connected inverter (GCI) of directly-driven wind turbine with permanent magnet synchronous generator (D -PMSG) under unbalanced grid conditions, a dual current-loop control strategy (DCC) which orien- ted on positive and negative voltage and current respectively was proposed to inhibit the DC voltage fluctu- ation and complete the wind generator un-off-line operation on grid faults. A 1.5MW D - PMSG with back-to-back IGBT frequency converter was simulated in the PSCAD/EMTDC environment, simulation results verify the correctness of the proposed control strategy.

关 键 词:直驱 风力发电 双电流闭环 不对称电网电压 

分 类 号:TM315[电气工程—电机]

 