GW4(A)-40.5DW型隔离开关导电带过热原因分析及改良设计  被引量:3

Analysis and Improved Design the Overheating Problem of the Conductive Strip of GW4(A)-40.5DW Disconnectors

在线阅读下载全文

作  者:刘小波[1,2] 黄斌[2] 苏文宇[2] 

机构地区:[1]武汉大学电气工程学院,武汉430072 [2]江西省电力公司超高压分公司,南昌330029

出  处:《高压电器》2012年第12期105-108,共4页High Voltage Apparatus

摘  要:GW4(A)-40.5DW型户外高压隔离开关在电网中应用广泛,而该型隔离开关导电带存在结构性缺陷,经常出现导电带过热问题。为保证电网安全,针对该型隔离开关导电带结构进行分析,设计出新型导电带并在现场成功实施更换改造。改造后的导电带端部设计为铝质结构并一次焊接成型,将导电带紧固部分设计为对穿螺丝的结构,将导电带软连接设计为铝质结构,解决原有结构性缺陷。GW4 (A)-40.5DW outdoor high-vohage disconnectors are widely used in the power grid. There is a structural defect in the conductive strip of this kind of disconnectors, causing a heat eonduetion problem frequently. To ensure the power grid safety, the internal structure of this conductive strip structure is analyzed, and a new conductive strip is designed, implemented replacement and reform in the seene successfully. Using aluminum in the end of the conductive strip structure and welding it at a time; designing the structure of conductive strip tighten part into blot core structure; using aluminum in the soft conductive strip connection to address the existing struetural defeet.

关 键 词:GW4(A)-40 5DW 隔离开关 导电带 改良设计 

分 类 号:TM564.1[电气工程—电器]

 