南方电网交直流滤波器调谐特性分析  被引量:3

Analysis on the Tuning Characteristics of AC&DC Harmonic Filters in China Southern Power Grid

在线阅读下载全文

作  者:龙启[1] 杨方明[1] 肖遥[1] 夏辉[1] 霍立海[1] 

机构地区:[1]中国南方电网超高压输电公司检修试验中心,广州510663

出  处:《南方电网技术》2012年第5期76-78,共3页Southern Power System Technology

摘  要:为了检测用于抑制电力系统的谐波、防止谐波对其造成危害的交直流滤波器的性能,根据各换流站设计规范书所规定的25℃下失谐度不超过1%,对南方电网所辖绝大多数直流滤波器和部分交流滤波器进行了调谐特性普测。通过测试发现被测交直流滤波器出现失谐的概率很低,说明交直流滤波器仍处于较好的运行状态。In order to detect the performance of AC&DC filters that are used to restrain the harmonic of a power system and prevent it from the harmonic harm, this paper makes a general check out to the most DC filters and parts of the AC filters in China Southern Power Grid (CSG) about their tuning characteristics according to the design specifications of disresonance degree less than 1% in the tempreture of 25℃. It is found that the probability of these filters being in disresonance is very much lower, showing they are in good operation.

关 键 词:超高压直流系统 滤波器 调谐特性 

分 类 号:TN713[电子电信—电路与系统]

 