通信基站应用热虹吸管换热机组的节能潜力  被引量:9

Energy Saving Potential for the Telecommunication Base Station Using a Thermosyphon Heat Exchanger

在线阅读下载全文

作  者:马国远[1] 陈杰[1] 周峰[1] 

机构地区:[1]北京工业大学环境与能源工程学院,北京100124

出  处:《北京工业大学学报》2013年第1期103-108,共6页Journal of Beijing University of Technology

基  金:国家自然科学基金资助项目(51076003)

摘  要:通过分析通信基站能耗特点及环境要求,建立其环控能耗模拟模型,对全国有气象数据城市的通信基站环控能耗进行模拟分析.以50 mm彩钢板围护结构为例,分析比较通信基站在空调单独运行和空调-热虹吸管联合运行条件下对环控能耗的影响,得到热虹吸管换热机组在全国范围内应用的全年节能效果,并绘制出节能效果分布图.分析结果表明,在我国绝大部分地区通信基站中,空调-热虹吸管换热机组联合运行可以取得明显的节能效果.Based on the analysis of the environmental requirements and energy consumption characteristics of the telecommunication base station (TBS) , the simulation model was established and the air conditioning power consumption for the TBS was calculated in the cities of China, where the climatic data can be found in the design handbook. Taking the sandwich panel with the thickness of 50 mm as the TBS envelope, the power consumption of an air conditioning coupled with or without a thermosyphon heat exchanger in the TBS and the energy saving potential for using ambient energy was calculated, and the energy saving rate was shown on the map of China by different colors. The results demonstrate that the operation mode of an air conditioning coupled with a thermosyphon heat exchanger for controlling the indoor temperature can bring enormous energy saving potential for the TBS located in China except the southern areas.

关 键 词:通信基站 热虹吸管换热机组 节能潜力 