摘 要:以乌鲁木齐室外气象参数为例,在回收排风能量上,从水泵能耗和风机能耗两方面对热管式间接蒸发冷却方式和传统的间接蒸发冷却方式的能耗进行了分析。研究结果表明,在总能耗方面热管式间接蒸发冷却方式的总耗功率为间接蒸发冷却方式总耗功率的5%左右。Taking the outdoor meteorological parameter of Urumqi as an example, the article mvestlgateo me energy consumption of fan and water pump for recovering the energy of exhaust air between the conventional indirect evaporation cooling air conditioning system and the evaporative cooling air-conditioning system with heat pipe heat exchanger. The results showed that the power consumption required for the evaporative cooling aironditioning system with heat pipe heat exchanger was much less than the one required for the conventional indirect evaporation cooling air conditioning system and was about 5% of the total power consumption required for the conventional indirect evaporation cooling air conditioning system.