UHV断路器非对称电流开断试验方法研究  被引量:6

Research on Test Method of Asymmetric Current Breaking Test for UHV Circuit Breaker

在线阅读下载全文

作  者:李刚[1] 姚斯立[1] 杜炜[1] 孙梅[1] 程茵[1] 王培人[1] 刘浩军[1] 

机构地区:[1]西安高压电器研究院有限责任公司,西安710077

出  处:《高压电器》2013年第4期20-24,共5页High Voltage Apparatus

摘  要:受设备容量的限制以及传统试验方法的局限,实验室很难对具有较长时间常数的特高压断路器进行非对称电流开断试验。笔者分析了该试验的原理,提出了一种新的电流补偿的试验方法。通过计算分析,论证了试验方法的等价性。1 100 kV断路器非对称电流开断试验采用了该试验方法,并顺利完成了多台产品的试验。这种试验方法还进行了推广应用,成功地完成了发电机断路器的非对称电流开断试验。Due to the limitations of equipment capacity and traditional test method, it is difficult for laboratory to carry out the asymmetric current breaking test for UHV circuit breaker with long time constant. This paper analyzed the test principle,and proposed a new current compensation test method. The equivalence of the test method was proved by calculation and analysis. This test method was successfully used in asymmetric current breaking test of several 1 100 kV circuit breakers. Moreover, it also used in asymmetric current breaking test of GCB.

关 键 词:特高压断路器 非对称电流 时间常数 电流补偿 面积等效 

分 类 号:TM561[电气工程—电器]

 