1000kV与500kV交流同塔输电线路的电晕损耗仿真及试验分析  被引量:9

Simulation and Experimental Analysis of Corona Loss of 1000 kV and 500 kV AC Transmission Lines on Same Tower

在线阅读下载全文

作  者:谢雄杰[1,2] 刘琴[2] 霍锋[2] 朱雷[3] 刘云鹏[3] 周国杨[3] 

机构地区:[1]武汉大学电气工程学院,武汉430070 [2]中国电力科学研究院,武汉430074 [3]华北电力大学电气与电子工程学院,北京102206

出  处:《高电压技术》2013年第3期592-596,共5页High Voltage Engineering

基  金:国家电网公司科技项目(SG0952)~~

摘  要:为了获得双回1 000kV与双回500kV交流同塔多回输电线路雨天电晕损耗的数据,开展了试验及仿真计算研究。采用有限元方法对电晕笼内和华东地区拟架设塔型的导线表面电场强度进行了计算;应用光纤数字化电晕损耗测量系统对电晕笼内4×LGJ-630和8×LGJ-630导线分别进行了干燥和淋雨条件下的电晕损耗测量;采用电晕损耗等效方法计算了淋雨条件下拟建塔型的电晕损耗。结果表明:干燥条件下,电晕笼内的4分裂导线和8分裂导线分别在施加电压为350kV和400kV时全线起晕;而在大雨条件下则没有明显的全线起晕拐点。计算得到双回1 000kV与双回500kV线路在大雨下单位长度(1km)电晕损耗分别为300.99kW和80.92kW。In order to obtain data of corona loss of AC multi-circuit transmission line with double-circuit 1 000 kV and double-circuit 500 kV on the same tower,we performed both test and simulation studies.The finite element method was used to calculate the field strength on the surface of wires in a corona cage and wires for the future East China towers.An optical digital corona loss measurement system was adopted to measure the corona loss of a 4×LGJ-630 wire and an 8×LGJ-630 wire in the corona cage under dry/rain conditions.The corona loss of the towers under rain condition was calculated by using the corona loss equivalent method.The result shows that,under the dry condition,both 4 bundled and 8 bundled conductors in the corona cage haloed all over when their voltages were 350 kV and 400 kV,respectively;however,there was no inflection point in the voltage which would induce all-over halo under the rain condition.According to the calculations,under the heavy rain condition,the corona losses of 1 km double-circuit 1 000 kV and double-circuit 500 kV were 300.99 kW and 80.92 kW,respectively.

关 键 词:1000kV 500kV 电晕笼 电晕损耗 电场强度计算 雨天 场强等效方法 

分 类 号:TM75[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象