500kV AIS变电站雷电过电压防护研究  被引量:1

Research on Thunderstorm Electricity Overvoltage Protection for 500 kV AIS Substation

在线阅读下载全文

作  者:吴静子[1] 丁胜强 甘凌霞[3] 李雷[3] 

机构地区:[1]长沙理工大学电气与信息工程学院,湖南株洲412000 [2]湖南湘潭电业局,湖南湘潭411101 [3]江西九江供电公司,江西九江332000

出  处:《电气开关》2013年第2期60-62,共3页Electric Switchgear

摘  要:将500kV变电站和进线段结合起来考虑,通过选择氧化锌避雷器的位置,在变压器安全的前提下设置不同的方案来对电抗器进行保护,采用ATPDraw进行仿真,并结合MATLAB对仿真结果进行计算。证明在电抗器前架设避雷器比在进线入口架设更能有效的防止雷电侵入波对电抗器及变电站内其他设备的危害。Considering a combining of a 500kV Substation with the Inlet lines, On the premise of ensuring the trans- former' s safety to choose the location of the MOA, putting forward different kinds of project to protect the reactor, Simu- lation analysis is presented over the ATPDraw and calculated the Simulation result on MATLAB. Proved that the location of the MOA to be setup in front of the reactor more effective than in Inlet lines erecting to prevent lightning invasion wave reactor and other equipment inside the substation harm..

关 键 词:变电站 氧化锌避雷器 ATPDRAW 雷电侵入波 

分 类 号:TM86[电气工程—高电压与绝缘技术]

 