回流比对前置反硝化BAF工艺脱氮性能研究  被引量:1

Impact of Reflux Ratio on the Denitrification Performance of Pre-denitrification Biological Aerated Filter

在线阅读下载全文

作  者:陆艳侠[1,2] 

机构地区:[1]安徽建筑工业学院,安徽合肥230000 [2]六安职业技术学院,安徽六安237000

出  处:《科技信息》2013年第7期164-165,共2页Science & Technology Information

摘  要:研究了采用前置反硝化曝气生物滤池工艺直接对生活污水进行处理,回流比对该工艺处理效果的影响。在一定范围内增大回流比有利于提高系统总脱氮率。根据试验结果,建议回流比选择2:1。在此条件下,COD去除率大于80%;NH4+-N去除率大于97%;总脱氮率大于75%。An experiment was carried out on domestic sewage using BAF with pre-denitrification process. The results show that reflux ratio on this system is significant. Within a certain range of increasing total nitrogen removal rate of the reflux ratio improves the system. According to the trial results, recommend that reflux ratio select 2:1. Under this condition, COD removal efficiency is greater than the 80%;NH4+-N removal efficiency greater than 97%; total nitrogen rate greater than 75%.

关 键 词:曝气生物滤池 前置反硝化 回流比 

分 类 号:X703.1[环境科学与工程—环境工程]

 