机构地区:[1]西安工程大学 [2]中国建筑西北设计研究院
出 处:《制冷与空调》2013年第3期88-92,共5页Refrigeration and Air-Conditioning
摘 要:首先介绍通信基站的特点及环境要求和蒸发式冷气机在通信基站中的应用,然后测试和分析福州某通信基站中蒸发式冷气机的运行参数,最后分析蒸发式冷气机与机房专用空调联动系统。研究结果表明:在福州气象条件下,通信基站中不能单独采用蒸发式冷气机,同时也不适宜使用蒸发式冷气机与机房专用空调联动系统(因为这会增加机房专用空调的负荷),只能单独采用机房专用空调为通信基站降温。First of all, the characteristics and environmental requirements of communication base station and the application of evaporative air-cooler into communication base station are introduced,and then operation parameters of evaporative air-cooler of one corn munication base station at Fuzhou are tested and analyzed,finally the linkage system of evaporative air-cooler and special air-conditioning for computer room is analyzed. Research results show that under such meteorological conditions at Fuzhou, the evaporative air cool er is not used alone for communication base station,and the same with the linkage system ( because the load of the special air-conditioning for computer room will increase), only the special air-conditioning for computer room is suitable.
关 键 词:蒸发式冷气机 通信基站 机房专用空调 湿热地区 运行模式 节能
分 类 号:TB65[一般工业技术—制冷工程] TN929.5[电子电信—通信与信息系统]