检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:陈国峰[1] 宋洪运[1] 邓先友[1] 常开忠[1]
机构地区:[1]中国南方电网超高压输电公司安宁局,云南昆明650217
出 处:《贵州电力技术》2013年第5期69-71,87,共4页Guizhou Electric Power Technology
摘 要:楚雄换流站开始孤岛调试第四阶段补充实验,当操作到试验项目1的联网转孤岛(16.20_S12)中的第12步:将极Ⅰ高端换流变分接头控制模式由定角度模式改为Udi0模式后极Ⅰ低端阀厅F5避雷器动作,导致的极Ⅰ双阀组闭锁。此次闭锁主要是由于极Ⅰ低端阀厅F5避雷器故障引起的,在以往高压直流输电工程中较为少见,文章将故障分析、处理过程作了总结。The decoupled (island) mode debugging test of Chuxiong Converter Station was began stage 4 - additional test, "networking -mode turn to decoupled -mode test" Step 12 (16.20_S12) : pole -I tapped control mode turned fixed -mode to Udi0 mode, pole - I low valve hall F5 arrester malfunction, then pole - I lock. The lock was mainly caused by the pole - 1 low valve hall F5 arrester fault, and it was rare in high -voltage direct current transmission project in the past. So the paper summarized the fault analysis and treating processes.