风电接入对继电保护的影响(七)——风电场送出电网继电保护配置研究  被引量:20

Impact of wind farm integration on relay protection(7): analysis of relay protection configuration for wind farm outgoing power grid

在线阅读下载全文

作  者:张保会[1] 原博[1] 王进[1] 王小立[1,2] 黄仁谋[3] 吴伟明[3] 

机构地区:[1]西安交通大学电气工程学院,陕西西安710049 [2]宁夏电力公司调度中心,宁夏银川750001 [3]海南电网公司,海南海口570100

出  处:《电力自动化设备》2013年第7期1-5,共5页Electric Power Automation Equipment

基  金:国家高技术研究发展计划(863计划)资助项目(2012-AA050201);Project supported by the National High Technology Research and Development Program of China(863 Program)(2012AA-050201)

摘  要:开展大规模风电场并网送出电网继电保护实时数字仿真(RTDS)试验,指出现有风电场送出电网继电保护存在的问题,给出风电场送出电网保护配置建议:110 kV送出线路的主保护采用分相电流差动保护,后备保护采用解微分方程算法的距离Ⅰ段,或将相量距离Ⅰ段保护延时0.15 s动作,同时配置常规距离Ⅱ、Ⅲ段及零序电流保护;送出变压器主保护采用差动保护,励磁涌流判据采用间断角鉴别、时差法等方法,后备保护配置复合过电流保护及零序电流方向保护;330 kV送出线路主保护配置2套独立工作的分相电流差动保护,采用电压突变量选相元件及基于零序分量的方向元件,后备保护配置与110 kV送出线路相同。The RTDS experiment is carried out for the relay protections of outgoing power grid of large-scale grid-connected wind farm and its existing problems are pointed out. The corresponding suggestions about the relay configuration are proposed:the main protection of 110 kV outgoing transmission line should adopt the phase-split current differential protection while its backup protection adopt the distance section Ⅰ using differential equation algorithm,or the time setting of phasor-based distance section l be prolonged by 0.15 s while the conventional distance section ,Ⅱdistance section Ⅲ and zero-sequence current protection be equipped ;the main protection of outgoing transformer should adopt the differential protection with the inrush current criterion using the dead angle identification,time-difference method,etc, while its backup protection adopt the compound over-current protection and zero-sequence current direction protection ;the main protection of 330 kV outgoing transmission line should adopt two independent sets of phase-split current differential protection with the voltage sudden-change phase selector and zero-sequence directional component while its backup protection adopt the same configuration as that of 110 kV outgoing transmission line.

关 键 词:风电场 继电保护 保护配置 RTDS试验 模型 

分 类 号:TM614[电气工程—电力系统及自动化] TM77

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象