330MW火电机组一次调频分析与优化  被引量:1

Analysis and optimization of primary frequency modulation of 300 MW coal-fired power generation units

在线阅读下载全文

作  者:王瑞[1] 张军 李昱 

机构地区:[1]宁夏电力公司能源科技有限公司,宁夏银川750011 [2]国电石嘴山发电有限公司,宁夏石嘴山753202

出  处:《宁夏电力》2013年第3期46-49,共4页Ningxia Electric Power

摘  要:针对国电宁夏石嘴山发电有限公司一次调频响应缓慢、调频幅度与设定值偏差较大等问题,对产生原因进行分析,提出优化方案。结果表明:数字式电液控制系统(Digital Electronic Hydraulic control system,DEH)一次调频存在滞后环节,严重影响调频速率及调频幅度,经过参数优化后,一次调频功能满足了电网调频要求。Aiming at the problems of primary frequency modulation responsed slowly,and larger de viation between the frequency modulation amplitude and setting value in Shizuishan Power Genera tion Co.,Ltd.,analyzes the reasons of problems occurred,puts forward optimization schemes.The anal ysis result shows that there is stagnant tache in primary frequency modulation of digital electronic hy draulic control system to influence badly the rate and amplitude value of frequency modulation.After the parameter optimization,the functions of primary frequency modulation basically meet the require ments of power grid.

关 键 词:一次调频 优化 火电机组 数字式电液控制系统 

分 类 号:TM39[电气工程—电机]

 