集中式双冷源温湿度独立控制空调系统的分析  被引量:3

Analysis of centralized temperature and humidity independent control air-conditioning system with dual-cold-source

在线阅读下载全文

作  者:王月莺 逯多威 马全石 

机构地区:[1]同方人工环境有限公司

出  处:《制冷与空调》2013年第7期112-116,共5页Refrigeration and Air-Conditioning

摘  要:介绍双冷源温湿度独立控制空调系统,并对该系统的高低温冷源负担的负荷进行分析。分析表明:该空调系统中高低温冷源负荷主要取决于第一机器露点。因此,进一步分析该系统的第一机器露点发现:机组能耗均随着第一机器露点的右移而减小,即高温机组冷冻水温度越高,系统越节能。该研究为空调系统的节能设计奠定了坚实的理论基础。Temperature and humidity independent control air-conditioning system with dual-cold-source is introduced, the cold source loads at low and high temperature are ana- lyzed. The results show that the cold source loads at low and high temperature are mainly decided by the first machine dew point. Furthermore,it is found out that the system's en- ergy consumption declines when first maehine dew point moving toward right position, which means that the ehilled water temperature higher,the system's energy consumption lower. The research establishes a firmly thesis base for the energy-saving design of air-con- ditioning system.

关 键 词:温湿度独立控制 负荷 第一机器露点 等焓线 等湿线 

分 类 号:TU831.3[建筑科学—供热、供燃气、通风及空调工程]

 