循环流化床锅炉中温过热器爆管分析  被引量:1

Analysis on Tube Burst of Mid-temperature Superheater on a Circulating Fluidized Bed Boiler

在线阅读下载全文

作  者:张志博[1] 姚兵印[1] 郭超 马剑民[1] 章春香[1] 杜涛 

机构地区:[1]西安热工研究院有限公司,陕西西安710032 [2]神华神东萨拉齐电厂,内蒙古包头014100

出  处:《华北电力技术》2013年第9期53-56,共4页North China Electric Power

摘  要:某循环流化床(CFB)锅炉中温过热器发生爆管,通过对爆管管样进行金相组织检验、化学成分分析、机械性能测试等,认为爆管是由于短时超温运行所致。为此,采取了使中温过热器管屏内蒸汽流向由"C"形改为"Z"形,在给水管路上增加憋压阀,燃烧调整等措施后,使机组的超温问题得到了显著的改善。Tube burst occurred on mid-temperature superheater of a circulating fluidized bed(CFB) boiler. Based on series of tests such as microstrueture examination,chemical composition analysis and mechanical property test, short time over-temperature operation was considered as the main reason. Thus, changing the mid-temperature superheater tube steam to flow from "C" to "Z" type,adding the back pressure valve in the water supply pipeline,combustion adjustment and other measures were taken, thus the problem of overheating is improved.

关 键 词:CFB锅炉 中温过热器 爆管 超温 改善 

分 类 号:TK223.31[动力工程及工程热物理—动力机械及工程]

 