中央空调高浓缩倍数水处理技术的研究及应用  

Research and Application of High-Concentration Water Treatment Technology of Central Air-Conditioners

在线阅读下载全文

作  者:张慧敏 梁遂芳 

机构地区:[1]河南省化工研究所有限责任公司,河南郑州450052

出  处:《河南化工》2013年第15期36-37,59,共3页Henan Chemical Industry

摘  要:针对中央空调冷却水系统存在的浓缩倍数高、结垢与腐蚀严重等问题,结合郑州地区水质特点,制备出了一种适合于高浓缩倍数运行的新型低磷水质处理药剂,磷含量≤6%(以P计)。静态、旋转挂片、动态模拟试验及实际应用结果表明:在循环水系统浓缩倍数4.0—6.0条件下,该处理剂可以取得较好的缓蚀阻垢效果。To cope with such problems as high concentration, and serious scaling and corrosion in the cen- tral air -conditioning cooling water system, a new low -phosphate water treatment agent is made accord- ing to the water quality characteristics of Zhengzhou, with at most 6% of phosphorus content, which is suitable for high concentration air - conditioning. Static, rotary coupon, dynamic simulation tests, and its application shows that this agent has a good effect in inhibiting corrosion and scale when the concentration multiple of the cyclic water system is between 4.0 and 6.0.

关 键 词:中央空调 浓缩倍数 水处理技术 缓蚀阻垢 应用 

分 类 号:TQ022.12[化学工程]

 