检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]中国科学院长春光学精密机械与物理研究所,长春130033
出 处:《电测与仪表》2013年第9期124-128,共5页Electrical Measurement & Instrumentation
摘 要:接地电阻是评价防静电工作区防静电能力的重要指标,在依据三点法采用钳形接地电阻测量仪ETCR2000测量接地电阻的前提下,本文提出了接地电阻测量不确定度评定的通用方法。首先对接地电阻测量原理进行了分析,建立了测量结果的导出数学模型,并确定了两类测量不确定度来源;其次,进行了接地电阻的测量不确定度评定,重点处理了测量结果的相关性问题;最终,在接地电阻测量值的范围较宽的情况下,推导出了通用的不确定度计算公式,从不确定度理论上保证了防静电工作区接地电阻测量的准确性。Earth resistance is an important index of anti-static ability for electrostatic discharge protected area. Adop- ting the Earth resistance tester ETCR2000 measuring the resistance by the three points method as a premise, the paper proposed universal uncertainty evaluation method for earth resistance' s measurement. First, the paper analyzed the measurement principle, established the deriving mathematical model of measurement results, and determined the two sources of measurement uncertainty; second, it evaluated measurement uncertainty of earth resistance, chiefly dealed with correlation of measurement result; Finally, the paper derived universal uncertainty formula, and ensured the measurement accuracy of EPA's earth resistance from uncertainty theoretically.
关 键 词:防静电工作区 接地电阻 三点法 不确定度 相关系数
分 类 号:TM93[电气工程—电力电子与电力传动]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.28