基于WAMS的南方电网低频振荡调度应对策略  被引量:10

WAMS-Based Dispatcher Strategy Against Low Frequency Oscillations in China Southern Power Grid

在线阅读下载全文

作  者:陈磊[1] 陈亦平[2] 戴远航[1] 刘恺[2] 张宇童[2] 洪成秋[1] 

机构地区:[1]清华大学电机工程与应用电子技术系,北京100084 [2]中国南方电网电力调度控制中心,广州510623

出  处:《南方电网技术》2013年第4期12-18,共7页Southern Power System Technology

基  金:国家自然科学基金项目(51007043);中国南方电网有限责任公司科技项目(K-ZD2012-015)~~

摘  要:南方电网区域间弱阻尼振荡已得到有效控制,但局部的以及机组原因引发的低频振荡问题仍然突出。探讨了调度运行中应对低频振荡的策略,从振荡前的预警预防和振荡发生后的紧急控制两个方面提出针对性应对措施。采用基于类噪声信号的模态参数辨识方法进行振荡前的预警预防,可摆脱对模型和参数的依赖,利用大量冗余数据提高结果可信度以及在线监视区间模式和局部模式的阻尼比,实现对危险模式的预警预防。采用基于振荡能量的振荡源定位方法进行振荡事故紧急处置,可以在振荡发生后快速准确的找到振荡的起因,定位振荡源,指导调度员采取针对性的措施快速平息振荡。利用实际振荡事故说明了所提调度应对策略的流程,并验证了所提方法的有效性。In China Southern Power Grid, the inter-area low damping oscillations have been eliminated effectively so far, but there are local and generator-induced low frequency oscillations yet. The dispatcher strategy for low frequency oscillations is discussed in this paper, including the early warning and prevention before oscillations and the emergency control of oscillations. The modal parameter identification method using ambient data is used for early warning and prevention of oscillations. The method avoids the dependence on the models and parameters, and with redundant data it can improve the credibility of the results and the damping ratios of both inter-area modes and local modes so to realize the early warning and prevention of critical modes. The oscillation source location method based on oscillation energy is adopted to find the cause of the oscillation, and to locate the oscillation source quickly and reliably, and to give dispatchers the instructions to damp the oscillation. The proposed dispatcher strategy is demonstrated in a real oscillation incident and its validity is verified.

关 键 词:南方电网 低频振荡 预警预防 类噪声信号 振荡能量 振荡源 

分 类 号:TM712.3[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象