作 者:王薇薇[1] 刘翀[1] 朱艺颖[1] 蒋卫平[1]
机构地区:[1]中国电力科学研究院,北京市海淀区100192
出 处:《电网技术》2013年第10期2732-2737,共6页Power System Technology
摘 要:上海地区有4回直流输电工程接入,逆变侧附近的变电站不断增多,变压器直流偏磁现象出现频繁。针对由多直流馈入而引起的交流变压器中性点直流电流增大的问题,建立了适用于这种情况的地区等值电网仿真模型。搭建了地上和地下2部分等值电网模型,地上部分为详细的4回直流输电系统模型以及上海地区交流网架的合理等值,地下部分为直流输电系统接地极电阻以及接地极到所研究交流变压器的地网电阻串并联拟合而成。利用三沪二回大负荷试验期间以及向上直流单极—大地方式运行期间实地测量的交流变中性点直流电流数据对该模型进行了校核,仿真结果证明本建模方法有效可行。最后基于此模型研究了多回直流处于不同运行方式对流入交流变直流电流的影响,为进一步研究多直流落点地区变压器中性点直流电流的抑制措施提供了参考。There are four HVDC power transmission lines connected with Shanghai power grid, so the number of substations near to the inversion stations is unceasingly increased and it makes the DC magnetic bias phenomena in transformers frequently occurred. In allusion to the increasing of DC current in AC transformer neutrals caused by different operation modes of multi-infeed HVDC transmission system, a simulation model of equivalent network suited to such condition is built. The built equivalent model is divided into two parts, namely the above-ground part and the underground part, the above-ground part includes detailed models of four HVDC power transmission lines and the reasonable equivalence of the frame of Shanghai AC power grid, and the underground part is the series-parallel fitting of earth electrode resistances of HVDC transmission systems with the grounding grid resistance from the earth electrode to the transformer to be researched. The built model is validated by the measured current data of AC transformer neutrals during the monopole high power test of the second ±500 kV HVDC project from the Three Gorges to Shanghai and that during mono-polar ground return operation mode of ±800 kV DC transmission project from Xiangjiaba to Shanghai, and simulation results show that the proposed modeling method is effective and feasible. Using the built model, the impacts of multi-infeed HVDC transmission system under various operation modes on DC current flowing in AC transformer are researched, and the research results are available for reference to further research on the measures to suppress neutral DC current of transformers located at the region with receiving ends of multi-infeed HVDC transmission system.
分 类 号:TM72[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.144.237.242