核电站常规岛直接蒸发冷却空调机组的测试分析  被引量:1

Testing and analysis of direct evaporative cooling air-conditioning unit applied on conventional island of nuclear power station

在线阅读下载全文

作  者:吴生[1] 黄翔[2] 李成成[2] 

机构地区:[1]西安工程大学科技处,陕西西安710048 [2]西安工程大学环境与化学工程学院,陕西西安710048

出  处:《西安工程大学学报》2013年第4期467-471,共5页Journal of Xi’an Polytechnic University

基  金:陕西省科技计划工业攻关项目(2012K0907);陕西省教育厅自然科学专项项目(12JK0804)

摘  要:结合工程实际要求,对海南、浙江、巴基斯坦等地区3个核电站工程的3台直接蒸发冷空调机组进行实验测试,得到送风量、风速、温度、相对湿度及阻力等机组的性能参数,满足3个区域的核电空调的要求.测试结果表明,填料厚度分别为100mm,200mm,300mm,其效率分别为72.7%,85.7%,93.6%.直接蒸发冷却空调机组不仅与填料厚度有关,而且与应用区域的干球、湿球温度有较为明显的关系.Three direct evaporative cooling air conditioning units used in Hainan,Zhejiang,Pakistan were tested.Performance parameters of unit,such as wind velocity,temperature,air relative humidity,the resistance were obtained.The test results show that the thickness of filling of direct evaporative cooling air-conditioning unit were 100mm,200mm,300mm,its efficiency was respectively 72.7%,85.7 %,93.6 %.The direct evaporation cooling air conditioning unit and packing thickness not only have a relationship but also with the dry bulb and wet bulb of application area.

关 键 词:核电站 填料效率 蒸发冷却空调机组 性能测试 

分 类 号:TU831.4[建筑科学—供热、供燃气、通风及空调工程]

 