基于振荡波检测系统的电力电缆局部放电波形研究  被引量:3

Power Cable Partial Discharge Waveform Analysis Based on Oscillatory Wave Test System

在线阅读下载全文

作  者:张国栋 田立斌[2] 王江林 李华[2] 

机构地区:[1]广东电网公司惠州供电局,广东惠州516001 [2]华南理工大学,广东广州510006 [3]广州安电测控技术有限公司,广东广州510665

出  处:《电工电气》2013年第11期45-49,共5页Electrotechnics Electric

摘  要:介绍了局部放电电流法检测局部放电的基本原理,给出了振荡波局部放电测试电路,对基于这一检测原理的振荡波局部放电测试系统检测的波形信号进行分析。研究表明振荡波检测系统检测的局部放电信号会受电缆传播特性的影响产生衰减,且检测的信号波形基本上呈现脉冲型和脉冲振荡衰减型两种形态。Introduction was made to the basic principle of partial discharge current method to test partial discharge. This paper gave the testing circuit of partial discharge based on oscillatory wave and analyzed waveform signals of oscillatory wave partial discharge test system based on the testing principle. The research result shows that the partial discharge signals affected by the propagation char- acteristics of power cable generated attenuation. The detected signal waveform basically presented pulse shape and pulse oscillatory at- tenuation shape.

关 键 词:振荡波 局部放电 脉冲电流法 

分 类 号:TM855[电气工程—高电压与绝缘技术]

 