检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]江西理工大学,江西赣州341000
出 处:《吉林电力》2013年第5期17-21,共5页Jilin Electric Power
基 金:江西理工大学校级研究生创新专项资金项目(编号YC2012-X13)
摘 要:对由三端同塔四回线构成的T形输电线路特点进行分析,运用12序分量法将T型线路四回线相电流、相电压分解为e,f,g,h四种分量,消除了四回线间互感。分析了反序h1序网的电气量特点,当T形同塔四回线发生故障时,从支接点T推算得出故障点的反序h1序电压与由故障支路母线处计算得到故障点的反序h1序电压相等。基于此等量关系构造测距新方法。大量ATP仿真数据表明,该方法测距准确,且精度不受故障类型、过渡电阻,系统运行方式等影响。The characteristics of teed circuit line with four-parallel lines on the same tower at three terminals have been analyzed in this paper. Twelve-sequence components method has been introduced to decouple mutual electromagnetic effect by decompose the phase current and phase voltage of teed circuit with four-parallel lines into e,f,g,h four components. When fault occurs on teed circuit with four-parallel lines on the same tower, the negative sequence hi-sequence voltage of the fault point calculated by the electrical measurements of the faulty branch bus is equal to that calculated by the equivalent negative sequence h-sequence electrical measurements of node T in the negative sequence h-sequence network. Based on this equivalent relation, a new method for fault line locating has been proposed. Lots of ATP simulation results show that the proposed fault locating algorithm is extremely high-accuracy and does not influenced by of fault type, transition resistance and system operating mode etc.
关 键 词:T形同塔四回输电线路 故障测距 12序分量法 反序h1序电压
分 类 号:TM755[电气工程—电力系统及自动化]