一起变压器近区短路冲击的诊断与分析  被引量:27

Diagnosis and Analysis of Nearby Short-circuit Impact on Transformer

在线阅读下载全文

作  者:邹国平 何文林 董雪松 李晨 付宝良 

机构地区:[1]浙江省电力公司电力科学研究院,杭州310014 [2]国家电网交流建设分公司,北京100052

出  处:《高压电器》2013年第12期95-98,103,共5页High Voltage Apparatus

摘  要:近区短路冲击是变压器损坏的重要原因,诊断变压器短路冲击后的受损情况并确定检修策略具有重要的意义。介绍了一起变压器近区短路故障导致绕组严重变形的事故。通过对变压器油色谱、三相运行电流、短路阻抗、直流电阻、电容量、频响曲线等数据的综合分析确定了变压器绕组发生严重变形。随后的返厂解体证实了诊断分析方法的有效性。Nearby short-circuit impact is the main reason of transformer damage, so diagnosing the transformer's status and choosing suitable management strategy are significant. This paper introduces a transformer accident of winding severe deformation caused by nearby short-circuit impact. By analyzing the dates of oil chromatographic, 3 phases' operation currents, short impedance, DC resistance, capacitance and frequency response curves, transformer winding deformation is conformed. The succeeding transformer disassembling indicates the effectiveness of diagnosis and analysis.

关 键 词:短路冲击 变压器 绕组变形 频响法测试 