检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]国网西藏电力有限公司运维检修部,西藏拉萨850000
出 处:《电网与清洁能源》2013年第12期61-65,69,共6页Power System and Clean Energy
摘 要:青藏联网工程正常运行期间,出现VCU(Valve Control Unit-阀控单元)光收发PS906异常,点火系统不能正常运行,PCP极控系统请求切换,导致换流阀不能正常导通,发生双极换相失败。在介绍青藏联网工程VCU的控制逻辑的基础上,详细分析了VCU故障导致换相失败的原因,并提出将相应设备接口环节双重化及PS900板卡A/B系统接入不同的PS912背板,避免阀组因单一的设备接口故障而引起直流系统故障,提高直流系统运行的抗干扰性和稳定性。During the operation of the QinghaiTibet Inter connection Project, an anomaly occurred to the S906 transceiver of the VCU(Valve Control Unit), leading to failure of the igni tion system. The PCP pole control system requested switching, thus the converter valve was not able to break over, finally causing failure of the bipolar commutation. On the basis of presentation of the VCU control logic used in the project, this article presents a detailed analysis of the causes for the VCU commutation failure, and proposes to double the appropriate device interface and insert different PS912 backplane for the A/B system of the PS900 board so that the system failure caused by a single device interface system failure can be avoided and the interference immunity and stability of the DC system be improved.
关 键 词:VCU(Valve C0ntrol Unit-阀控单元) 换相失败 PS900 PS906 PS912
分 类 号:TM721.1[电气工程—电力系统及自动化]