检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]重庆市电力公司,重庆400014 [2]国网智能电网研究院中电普瑞科技有限公司,北京100192
出 处:《电力系统保护与控制》2014年第1期54-61,共8页Power System Protection and Control
摘 要:随着冲击性负荷的日益增多,迫切需要对大量冲击性负荷接入电网时所引发的电能质量问题进行有效的分析。结合重庆电网,提出了分析大量冲击性负荷接入系统时的电能质量评估方法并给出了综合的治理方案。首先基于电流的实测数据建立了冲击负荷的新型拟合模型,并结合ward等值理论和戴维南定理多电势转化方法搭建了重庆地区的等值电网,将冲击负荷模型接入等值电网中,以此为平台研究了多个冲击性负荷接入对重庆电网电能质量的综合影响。针对电能质量超标的情况,分析了提高冲击负荷接入的电压等级、加装滤波器或SVC等治理措施,并结合重庆电网冲击负荷实测电能质量数据提出了治理方案。在PSCAD中搭建了仿真模型,验证了分析结果的有效性和准确度,为冲击负荷接入重庆电网的综合治理提供了理论参考。As the number of impact loads increases, there is an urgent need to develop a valid method to analyze the power quality problems caused by these multiple impact loads. Taking the Chongqing electric power system as an example, the paper presents an evaluation method for the power quality problem when multiple impact loads are connected into the system, and proposes a comprehensive treatment scheme. A new impact load model is constructed based on the fitting measured data, while the regional equivalent grid is established based on the Ward equivalent and multi-potential equivalent in Thevenin Theorem, then the combined effects on the power quality of Chongqing Grid are studied when multiple impact load models access the equivalent grid. For the case of excessive power quality, several control measures are analyzed, such as increasing access voltage level, installing filter or SVC, and treatment schemes are proposed based on the measured power quality data of impact loads in Chongqing Grid. The validity and accuracy of analysis results are verified by building simulation model in PSCAD, and theoretical reference for the comprehensive treatment when impact loads access Chongqing Grid is provided.
关 键 词:冲击负荷 区域等值电网 谐波畸变 电压波动 治理措施
分 类 号:TM711[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.15