110kV鹿邑变电站接地网改造研究  被引量:1

Transformation of 110 kV Luyi Substation Grounding Grid

在线阅读下载全文

作  者:成文杰[1] 张竞[1] 史宏伟[2] 尚龙龙 

机构地区:[1]重庆大学输配电装备及系统安全与新技术国家重点实验室,重庆400030 [2]河南省电力公司周口供电公司,河南周口466000

出  处:《华北电力技术》2013年第12期41-45,共5页North China Electric Power

基  金:国家创新研究群体基金(51021005)

摘  要:降低变电站的接地电阻、接触电压和跨步电压对保障变电站人员、设备安全特别重要。110 kV鹿邑变电站因运行日久,地网腐蚀严重,已不能满足安全运行的要求。针对鹿邑变电站原有地网设计不规则的现状,运用CDEGS软件建立地网模型并仿真计算,提出两种地网改造方案。通过仿真分析结果得出敷设垂直接地极能有效地改善地网的接地性能。To reduce the substation grounding resistance, step and touch voltages is especially important for security of personnel, equipment of substation, l lOkV Luyi substation has been running for a long time, serious corrosion cannot meet the requirements of safety operation. In view of the current situation that Luyi substation grounding grid design is irregular,using CDEGS software to build network model and simulation calculation,this paper puts forward two kinds of network reconstruction scheme. The simulation results show the laying of vertical grounding can effec- tively improve grid grounding performance.

关 键 词:接地电阻 垂直接地极 接触电压 跨步电压 

分 类 号:TM63[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象