检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]中国南方电网电力调度控制中心,广东广州510623
出 处:《电力科学与技术学报》2013年第4期92-97,共6页Journal of Electric Power Science And Technology
基 金:国家自然科学基金(70871074)
摘 要:500kV超高压线路高阻接地时,初始阶段故障电流突变量很小,主保护有可能拒动.随着接地故障电阻变小,故障电流增大后由后备保护动作切除,而后备保护较长时间切除故障可能影响电网稳定.介绍"7·10"500kV花博甲线高阻接地故障差动保护拒动事件,分析不同运行方式对两侧故障电气量的影响,总结现有差动保护启动判据的缺陷,并提出采用近故障侧保护装置启动判据、负序电压启动判据等改进措施,有效提高了高阻接地时差动保护的动作可靠性.When high-resistance grounding fault occurs in 500 kV EHV line, the sudden change of fault current is not significant at the initial stage, so main protection may refuse to operate. As the grounding resistance decreases and the fault current increases, the fault can be cleared by the back-up protection action, which may impact the power grid stability seriously. A differential protection failure event was introduced in this paper, which occurred on Hua-Bo 500 kV line in Guangzhou province on July 10. The effect of operation modes on fault characteristics at both terminals was analyzed. Based on the deep research of existing differential protection methods, the improvement measures including the near fault terminal characteristics criterion and negative sequence voltage criterion was presented. They can highly improve the reliability of differential protection operation, especially when high impedance grounding fault occurs.
关 键 词:超高压线路 高阻接地故障 差动保护 负序电压判据
分 类 号:TM762[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:18.223.28.135