导纳型失磁保护校验方法探究  被引量:1

Calibration Method for Excitation Loss Protection with Admittance

在线阅读下载全文

作  者:陈寿根[1] 尹亮 吴冰峰 罗裕柯 

机构地区:[1]中广核工程公司大亚湾核电运营公司,518124 [2]红沿河核电有限公司,辽宁116319

出  处:《华东电力》2014年第1期198-202,共5页East China Electric Power

摘  要:大多数失磁保护都是阻抗型保护,保护定值为2个阻抗圆,常规的继电保护测试仪都能方便地测出阻抗圆的轨迹。导纳型失磁保护与阻抗型失磁保护不同,其定值为3个导纳值和3个导纳角。由于导纳轨迹在导纳平面内伸向无穷远,继电保护测试仪无法直接测出它的整个轨迹。手动测试导纳轨迹上的几个动作点的校验方法没有验证整个导纳轨迹。导纳转换阻抗法是通过数学方法将导纳轨迹转换为阻抗轨迹,然后通过测得的阻抗轨迹来间接验证整个导纳轨迹。尽管转换过程比较复杂,但2台机组的试验成功验证了理论推导出的阻抗轨迹与实际测得的阻抗轨迹完全一致。Most excitation loss protections are impedance protection with two impedance networks as protection setting values, whose trajectory can be easily measured by the conventional relay protection test device. To be different, the excitation loss protection with admittance has three admittance values and three admittance angles. Due to the infinity bf admittance loci in admittance plane, relay protection test device cannot directly measure the entire trajectory. The calibration method recommended by the equipment manufacturer is to manually test a few action points on the admit-tance loci, but not the entire admittance loci. Impedance conversion by admittance method is to convert admittance trajectory to impedance trajectory through mathematical method, and then through the measured impedance trajectory to indirectly verify the entire admittance loci. Despite the complexity of the conversion process, the experimental suc-cess on 2 units verifies that the theorized impedance trajectory is completely consistent with the measured impedance trajectory.

关 键 词:导纳型失磁保护 数学转换 阻抗圆校验 

分 类 号:TM307[电气工程—电机]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象