空冷风机组运行性能优化研究  被引量:7

Optimization on operation performance of air cooling fan cluster

在线阅读下载全文

作  者:董康田[1] 闫宏[1] 孙大伟[1] 王星[1] 

机构地区:[1]西安热工研究院有限公司,陕西西安710032

出  处:《热力发电》2014年第1期52-56,共5页Thermal Power Generation

摘  要:空冷岛风机风量分布不均的主要原因是空冷风机选型统一,空冷风机转速调节单一.对某600 MW直接空冷机组空冷风机系统在不同环境风下空冷风机的运行性能进行了研究.结果表明,通过提高风机转速,且对空冷岛不同位置风机区别调节,克服了群效应及环境风对空冷风机系统的影响,各位置空冷风机风量均达到了500~525 m3/s(设计风量为499.4 m3/s),确保了空冷机组的正常运行.Analysis show the same air cooling fan type and single regulation mode caused uneven distribution of the air flow from air cooling fans. The operation performance of air cooling fans under different environmental wind conditions was investigated for a 600 MW direct air cooling u- nit. The results show that, by enhancing the air fan speed and regulating the air fan at different lo- cations discriminately,the influence of cluster effect and environmental air on the air cooling sys- tem was overcome. Thus the air flow of each air cooler reached the design value,ensuring the u- nit ' s normal operation.

关 键 词:直接空冷机组 风机 运行性能 主动调节 区别调节 

分 类 号:TK124[动力工程及工程热物理—工程热物理]

 