复合与瓷和玻璃绝缘子直流覆冰闪络特性比较  被引量:8

Comparison on DC Icing Flashover Performance of Porcelain, Glass, and Composite Insulators

在线阅读下载全文

作  者:向泽[1] 蒋兴良[1] 张志劲[1] 胡琴[1] 董冰冰[1] 王尧玄[1] 

机构地区:[1]重庆大学输配电装备及系统安全与新技术国家重点实验室,重庆400030

出  处:《高电压技术》2014年第2期434-440,共7页High Voltage Engineering

基  金:国家重点基础研究发展计划(973计划)(2009CB 724501/502/503);国家创新研究群体基金(51021005)~~

摘  要:污秽覆冰环境下绝缘子电气特性是覆冰地区输电线路外绝缘选择的基础,然而国内外针对不同材质绝缘子覆冰闪络特性的对比研究甚少。为此,在人工气候室内模拟覆冰气象条件,采用恒压升降法对3种不同材质绝缘子进行了大量覆冰直流闪络试验研究。分析试验结果得出了目前常用3种绝缘子在覆冰污秽条件下的直流闪络特性,结果表明:严重覆冰条件下,复合绝缘子电弧闪络梯度略高于瓷和玻璃绝缘子,且其污秽特征指数略小;覆冰水电导率和表面污秽对电弧闪络梯度的影响特征指数有明显差异。最后提出了绝缘子串覆冰水电导率及表面污秽共同作用时的直流电弧闪络梯度校正公式。研究结果可为覆冰地区输电线路外绝缘的选择和设计提供参考。The electrical performance of insulators in freezing condition is a basis for selecting external insulation of transmission lines and substations in icing regions. However, little research has been dedicated to the comparison between composite, porcelain and glass insulators in their DC icing flashover performances. Therefore, we analyzed these perfor- mances on the basis of a number of experiments carried out in an artificial climate chamber. The results indicate that, in severe icing condition, compared porcelain and glass insulators, ice-covered composite insulators have greater flashover voltage grads (FVG) but smaller characteristic exponents that characterize the influence of pollution on icing FVG. The characteristic exponents vary obviously with different salt deposit density and freezing-water conductivity. We also pro- posed a calculation expression for correcting the minimum DC FVG of iced insulators in single or coexisting conditions of salt deposit density and freezing-water conductivity. The results could be referred by the selection and design of trans- mission lines' external insulation in ice regions.

关 键 词:绝缘子 覆冰水电导率 表面污秽 直流 覆冰闪络特性 电弧闪络梯度 

分 类 号:TM216[一般工业技术—材料科学与工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象