净空高度对自动喷水灭火系统控火性能影响试验研究  被引量:4

Experimental research on the influence of height on the sprinkler system extinguishing performance

在线阅读下载全文

作  者:杨丙杰[1] 王珺[1] 

机构地区:[1]公安部天津消防研究所,天津300381

出  处:《消防科学与技术》2014年第2期164-166,共3页Fire Science and Technology

基  金:国家"十二五"科技支撑计划项目(2011BAK03B04-2)

摘  要:为研究喷头安装高度对自动喷水灭火系统控火性能的影响,分别在安装高度为3m和8m的情况下,选取目前应用最为广泛的标准喷头开展对比试验,从动作时间、动作个数、动作温度以及货物烧损量等方面进行对比分析。结果显示,在2种安装高度下,喷头均能有效控火,但安装高度提升不仅造成喷头动作时间延迟,还使得喷头动作个数、货物烧损量等明显增加。In order to study the influence of height on the sprinkler system extinguishing performance,comparative tests were conducted at the height of 3 m and 8 m,and using the most widely used standard sprinkler.The operation time,number of sprinklers active,operating temperature and burning cargo were compared and analyzed.Results showed that the fire can be extinguished effectively under 2 installation height,but when the height is bigger,the operation time was delayed,the number of sprinklers active increased,and the burning cargo increased too.

关 键 词:自动喷水灭火系统 安装高度 控火性能 动作时间 

分 类 号:X924.4[环境科学与工程—安全科学] TU892[建筑科学]

 