Finite Element Method Applied to Fuse Protection Design  

Finite Element Method Applied to Fuse Protection Design

在线阅读下载全文

作  者:李森 宋执权 张明 许留伟 李金超 傅鹏 王敏 董琳 

机构地区:[1]College of Electrical and Electronic Engineering,Huazhong University of Science and Technology [2]State Key Laboratory of Advanced Electromagnetic Engineering and Technology [3]Institute of Plasma Physics,Chinese Academy of Sciences [4]China International Nuclear Fusion Energy Program Execution Center

出  处:《Plasma Science and Technology》2014年第3期294-299,共6页等离子体科学和技术(英文版)

基  金:supported by the National Magnetic Confinement Fusion Science Program of China(Nos.2010GB108001 and 2013GB113003)

摘  要:In a poloidal field (PF) converter module, fuse protection is of great importance to ensure the safety of the thyristors. The fuse is pre-selected in a traditional way and then verified by finite element analysis. A 3D physical model is built by ANSYS software to solve the thermal- electric coupled problem of transient process in case of external fault. The result shows that this method is feasible.In a poloidal field (PF) converter module, fuse protection is of great importance to ensure the safety of the thyristors. The fuse is pre-selected in a traditional way and then verified by finite element analysis. A 3D physical model is built by ANSYS software to solve the thermal- electric coupled problem of transient process in case of external fault. The result shows that this method is feasible.

关 键 词:PF converter thyristor protection fuse verification finite element method 

分 类 号:TM563[电气工程—电器]

 