35kV新旧导线载流量与温升对比分析  被引量:3

Comparative Analysis on the Carrying Capacity and Temperature Rise of New and Old 35 kV Conductors

在线阅读下载全文

作  者:周文斌[1] 王新颖[2] 白俊峰[2] 鞠彦忠[2] 

机构地区:[1]广东电网公司阳江供电局,广东阳江529500 [2]东北电力大学,吉林吉林132012

出  处:《南方电网技术》2014年第2期92-95,共4页Southern Power System Technology

摘  要:通过用不同的测温计测量老旧导线和新导线的温度,在室内模拟架空输电线路的运行状态,对比分析了阳江35 kV老旧导线与未服役的新导线的载流温升性能。由理论分析,发现老旧导线的辐射散热功率高于未服役新导线,未服役新线的辐射散热功率比老旧导线少46%左右;由试验结果分析得出:LGJ70/10导线在相同的电流值下,未服役新导线的温升比老旧导线的温升低11%左右。By using different thermometers to measure the old and the new conductors' temperature,by simulating the overhead transmission lines' running indoor,and comparative analysis of the performance of the carrier temperature of Yangjiang 35 kV old conductors and new ones. By the theoretical analysis,we found the old wires' radiated heat power higher than the new conductors. The heat radiated power of the new conductors are less than about 46% of the old ones; Analysis of test results obtained by the wire at the same current value,the new LGJ70 /10 conductors service temperature is lower than the old ones about 11%.

关 键 词:导线 载流量 试验 

分 类 号:TM726.3[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象