检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]中国电力科学研究院,北京100085 [2]华北电力大学(北京),北京102206 [3]北京首钢设计院,北京100043
出 处:《电网技术》2001年第7期56-59,71,共5页Power System Technology
摘 要:并联电容器组是目前电网中普遍用来补偿无功的装置 ,而无源滤波器通常用来吸收谐波源产生的谐波电流 ,并兼顾无功补偿。文中以工程实例为依据 ,用电力系统谐波计算程序 CHP对补偿电容器组串联电抗对无源滤波器性能的影响进行了分析计算。结果表明 ,无源滤波器与补偿电容器组并联运行情况下 。At present the parallel capacitor banks are the widely used devices to compensate reactive power in power network, and to absorb the harmonic currents caused by harmonic sources the passive filters consisting of reactors and capacitors are applied and at the same time the reactive power compensation is performed. On the basis of paractical engineering example, The affection of compensating capacitor bank in series with reactor on passive filter is analyzed and calculated by CYME Harmonic Program (CHP) imported from Canada. Calculation result shows that when passive filter is operated in parallel with compensating capacitor bank in series with different reactor, both the frequency characteristics of the impedance of power supply system and the performance of filter will be affected.
关 键 词:电力系统 无功补偿 补偿电容器 串联电抗 无源LC滤波器
分 类 号:TM714.3[电气工程—电力系统及自动化] TN713[电子电信—电路与系统]