架空线路短路故障点测距装置研制  

Study on On-Line Short Circuit Fault Locator for Power Transmission Line

在线阅读下载全文

作  者:吴勇军[1] 刘政波[1] 陈祥初[1] 

机构地区:[1]第二炮兵第四研究所,北京100085

出  处:《电力自动化设备》2001年第7期53-54,共2页Electric Power Automation Equipment

摘  要:介绍了 1种新的架空线路故障测距方法。该方法只测量线路的电抗 ,测量精度不受短路过渡电阻的影响。根据该方法研制成以 80C196单片机系统为主的架空线路故障测距装置。经电力系统模拟试验 :该装置对故障点能准确定位 ,测量误差在 3%以内 ,具有较高的工程实用价值。A new fault location method for power transmission line is proposes,by which only the line reactance is to be measured and the fault interim resistance will not effect the measuring precision. A fault locator for power transmission line using 80C196MCU system as its core is developed based on the method. The simulation test shows that the fault location can be correctly pointed out, and the measuring error is within 3%. Therefore, it has a higher practical value in engineering.

关 键 词:输电线路 架空线路 短路 故障点测距装置 

分 类 号:TM726.3[电气工程—电力系统及自动化]

 