机构地区:[1]广西大学,广西壮族自治区南宁市530004 [2]广西电力试验研究院,广西壮族自治区南宁市530023
出 处:《电网技术》2001年第9期56-60,共5页Power System Technology
摘 要:测量电容式电压互感器的一次绕组对二次绕组及地的阻抗特性时在某种接线方式下阻抗会呈感性 ,这将使电容式电压互感器的介损测量产生异常结果。当阻抗呈容性时对介损测量影响较小。文中详尽分析了各种不同的测量接线方式下中间变压器对电容式电压互感器介损测量产生的影响 。In the measurement of impedance among primary winding, secondary winding and ground of capacitive potential transformer it is discovered that under a certain wiring mode the impedance may be inductive and this phenomena may cause abnormal result in the dielectric loss measurement, while the impedance is capacitive the affect on the dielectric loss measurement will be reduced to a small extent. In this paper the affect of intermediate transformer on the dielectric loss measurement of capacitive potential transformer under different wiring modes is analyzed in detail, the results of analysis is available for reference in site measurement of capacitive potential transformer.
分 类 号:TM934.32[电气工程—电力电子与电力传动] TM451.2