检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]哈尔滨工程大学建筑工程学院,黑龙江哈尔滨150001
出 处:《应用科技》2001年第11期14-16,22,共4页Applied Science and Technology
摘 要:冷却吊顶空调系统的节能性和新风量的选取直接相关 ,以北京市某办公楼为例 ,分别计算出该建筑采用常规FP +新风系统和冷却吊顶空调系统时的能耗 ,并进行分析比较 ,结果表明 ,当冷却吊顶系统的新风再热后送入室内时 ,若系统新风量较大 ,从运行能耗角度来看 ,应优先选取冷却吊顶系统。There is direct relation between cooling ceiling air_conditioning system's function of saving energy and choosing the volume of fresh air. This paper set a certain office building in Beijing as an example, calculated, compared and analysed the two system's difference between the fan_coil units plus fresh air system and cooling ceiling air_conditioning system's energy exhaust. In the end, the result shows that when cooling ceiling air_conditioning system's fresh air reheated before it is sent into the room, if there is a large amount of fresh air in the system, from the operate energy exhausted point of view, it is wise to select the cooling ceiling air_conditioning system.
分 类 号:TU831.3[建筑科学—供热、供燃气、通风及空调工程]