提高电抗器线圈层间绝缘块的工频耐压强度  

Improving the Power Frequency Withstand Voltage of the Insulating Piece for the Reactor

在线阅读下载全文

作  者:高良玉[1] 郭文元[1] 沈玉琢[1] 

机构地区:[1]同济大学电气工程系,上海200331

出  处:《高电压技术》2002年第1期27-27,51,共2页High Voltage Engineering

摘  要:南方潮湿地区电容补偿装置用电抗器常有烧损故障 ,一个主要原因是线圈层间绝缘垫块湿闪电压降低。对线圈层间绝缘垫块施加多种复合材料涂层后的工频耐压试验结果表明 :氨基绝缘清漆和聚偏氟的复合型绝缘涂层可明显改善线圈层间绝缘块的湿闪电压并减小湿闪场强下降率 ,从而提高线圈层间绝缘块在潮湿环境下的工频耐压强度。The fault of reactor of compensation device used in substation of electric railway is studied. The causes of fault are: 1) overvoltage causes the flashover or breakdown between layers of coil, 2) the surface moist flashover of insulating piece is reduced. The test of power frequency withstand voltage is made. The results show the compound- coating can increase the moist flashover voltage and the voltage withstand intensity of insulating piece at moist condition.

关 键 词:电抗器 线圈 绝缘块 工频耐压强度 复合涂层 

分 类 号:TM47[电气工程—电器]

 