检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]聊城发电厂,山东省聊城市252033 [2]聊城电业局,山东省聊城市252053
出 处:《电网技术》2002年第2期84-87,共4页Power System Technology
摘 要:通过对一起保护误动事故进行的理论分析 ,指出 JD-13型发电机两点接地保护装置在设计原理上存在着缺陷 ,不但一点频繁接地时容易发生误动 ,而且 ,在不同位置发生间隔时间很短的瞬间接地时 ,也可能发生误动。针对这一缺陷提出了两种解决方案 ,并通过比较 ,选择了一种恰当的解决方案。试验表明 ,该方案能克服了原设计中的缺陷 ,能满足运行的需要。After the theoretical analysis of a misoperation occurred in JD 13 type of protection against dual grounding fault of rotor winding, it is discovered that there is a defect in the design of the protective device which not only may easily make the device misoperate under rotor winding grounding frequently occurring at the same position, but also under the instantaneous grounding occurring at two different positions with very short time interval. To revise this defect two improvement methods are described in this paper and a suitable one is selected. Test results show that the selected method can correct the defect in the original design of the device and meet the need of operation.