不同微孔曝气设备对饮用原水增氧效果中试研究  被引量:1

Pilot Study on Oxygen Enhancement Effect of Different Microporous Aeration Equipment For Drinking Water Source

在线阅读下载全文

作  者:顾贇 卿杰 巢路 GU Yun;QING Jie;CHAO Lu(Upstream Water Source of Huangpu River Co.,Ltd,200233Shanghai,China;Shanghai Investigation Design&Research Institute,200434,Shanghai,China)

机构地区:[1]上海黄浦江上游原水有限公司,200233 [2]上海勘测设计研究院有限公司,上海200434

出  处:《水处理技术》2018年第12期117-120,共4页Technology of Water Treatment

基  金:上海市科委科研计划项目(15DZ1205602)

摘  要:选取3种不同的微孔曝气设备,针对其向饮用水原水的增氧效果进行了中试研究。结果表明,微纳米气泡设备的增氧效果最好,年平均DO含量提升率为15.80%,氧利用率为11.8%;楔形微孔曝气器和微孔橡胶膜管的增氧效果比较接近,年平均DO含量提升率分别为9.74%、9.08%,氧利用率分别为0.77%和0.68%。3种设备在各季度的季平均DO含量提升率和氧利用率2方面均表现为春季>夏季>秋季>冬季。微孔曝气设备的DO含量提升率和氧利用率会受水温和进水DO含量的影响,进水DO含量越接近饱和含量,其提升率和氧利用率则越低。Three different kinds of micropore aeration equipment were selected to conduct pilot-scale studies on the oxygenation enhancement effect of the drinking water resource. Results showed that the micro-nano aeration equipment had the best oxygenation effect. The annual average DO content increase rate was 15.80%, and the oxygen utilization rate was 11.8%. The aerobic effect of the wedge-shaped ring and the rubber membrane tube was relatively close. The annual average DO content increase rate was 9.74% and 9.08%, and the oxygen utilization rate was 0.77% and 0.68%, respectively.The seasonal average DO content increase rate and oxygen utilization rate of the three facilities in each season were spring > summer > autumn > winter.The DO content increase rate and oxygen utilization rate of the microporous aeration equipment were affected by the water temperature and the DO content in the influent. When the DO content of the influent water was closer to the saturation content, and the increase rate and oxygen utilization rate were lower.

关 键 词:微孔曝气 饮用水原水 增氧 中试 氧利用率 

分 类 号:TU991.27[建筑科学—市政工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象