1000MW机组发电机密封油管道安装位置对氢气泄漏的影响分析  被引量:2

Influence of Installation Position of Sealing Oil Pipeline on Hydrogen Leakage of 1 000MW Generator Unit

在线阅读下载全文

作  者:陆杰[1] LU Jie(Shanghai Power Construction Startup & Testing Institute,Shanghai 200031,China)

机构地区:[1]上海电力建设启动调整试验所,上海200031

出  处:《电力与能源》2018年第6期892-893,896,共3页Power & Energy

摘  要:介绍了对某1 000MW电厂发电机氢气泄漏严重问题的检查情况,通过对发电机密封油及氢气系统的研究,发现了由于密封油系统油氢差压阀的两根信号取样管(氢汽压力和密封油压力信号取样管)的安装位置问题而导致取样管内油静压无法合理消除和补偿情况,导致了发电机氢气泄漏量大,并提出了改进措施。The serious problem of hydrogen leakage of a generator in a 1 000 MW power plant is introduced and analyzed.Through the study of the sealing oil and hydrogen system,it was found that the installation position of two signal sampling tubes(hydrogen vapor pressure and sealing oil pressure signal sampling tube)due to the oil hydrogen differential pressure valve of the sealing oil system caused the hydrostatic pressure in the sampling tube to be unable to fit in.The elimination and compensation of the generator made the sealing oil pressure of the generator fail to meet the design requirements,resulting in large leakage of hydrogen from the generator.

关 键 词:1000MW发电机组 密封油系统 氢气泄漏量指标 

分 类 号:TM621[电气工程—电力系统及自动化]

 